Level Converter of the EQUOBOX system.
M-Bus level converter for managing up to 60 devices.
Field module for reading data from M-Bus meters. Stand-alone module for use with SIN.EQSW1.
M-Bus slave interface for use as booster/repeater to extend the M-Bus network by a further 60 devices.
24V AC/DC power supply
ELECTRICAL CHARACTERISTICS |
|
Rated Voltage |
24Vdc +/- 10% (Rev. HW 1.0 or if not specified) 24Vdc +/- 10%, 24Vac (min 20Vac, max 40Vac) 50/60Hz for HW 2.0 versions |
|
(*) It is suggested to prefer continuous power supply (dc) in order to limit thermal dissipation and consumption |
Installation category |
Class III |
Rated consumption |
3W + (0.07* number of M-Bus loads) |
Maximum consumption |
12W |
MECHANICAL FEATURES |
|
Operating temperature range |
From -20°C to +55°C |
Storage temperature range |
From -25°C to +65°C |
Dimensions |
90x71x62 mm (HxLxD) – DIN |
Installation type |
35mm DIN bar (EN60715) |
Protection rating |
IP20 (EN60529) |
Connections |
M-Bus Slave: to connect as a repeater/extender M-Bus Master: for connection to the M-Bus meters Mini-USB Type B: for connection to the EQUOBOX TOOLKIT (SIN.EQSW1) software |
Installation and positioning |
It is suggested not to place the device in adherence with others in order to avoid their overheating |
M-BUS SECTION |
|
Reference standard |
EN13757-2 (Physical Layer) |
Baud rate |
Min. 300bps – Max. 9600bps |
M-Bus-RS232 isolation |
1KV AC |
M-Bus-USB isolation |
1KV AC |
Max. number of M-Bus devices (loads) |
60 |
Max. number of Repeaters |
Unlimited in stand-alone mode for reading current data via an RS232 or USB connection Four (4) as slaves to the EQUOBOX RTU M-Bus |
Transmission speed |
Minimum: 300bps Typical: 2400bps Maximum: 9600bps |
Bus voltage |
42V – 30V |
Short circuit protection |
Yes |
SIGNALING LEDs |
|
USB Activity (orange LED) |
Connection status with EQUOBOX TOOLKIT software |
TXD (Green LED) |
Transmission status on the M-Bus Master |
RXD (Green LED) |
Reception status from the M-Bus Master |
M-Bus ERROR (Red Led) |
Indicates a short circuit or the overloading of the M-Bus |
M-Bus Ready (Green Led) |
Indicates level converter is ready to work |
POWER (Red Led) |
Indicates the correct power supply of the device |
Check the Presetting List for pre-set objects with the Equobox system